In This Store
Product Name:AH Refrigeration heating temperature control system
Price(USD):0.00
Company:Wuxi Guanya Refrigeration Technology Co., Ltd. (LNEYA)
Factory Location: NO.2 Building,NO.207 Hongyun Road,New District,Wuxi,Jiangsu, China
Main Sales Markets: North America,Central/South America,Western Europe,Eastern Europe,Australasia,Asia,Middle East,Africa
Monthly Production Capacity: 10
Packaging Information: wooden case
Delivery Lead Time: 25 WORKING DAYS BY SEA
Sample Provided: no
Payment Terms: T/T
Description
Applied to the glass reactor,metal reactor,bioreactor for cooling&heating and thermostatic control,particularly suitable for controlling the required heat or heat release in the process of reaction.
-25℃~200℃
Suitable for high heat release-----Refrigeration heating temperature control system
AH series-
is applied to SUS Reactor,temperature difference >150℃
Rapid cooling at high temperature reaction
Polymerization reaction
Rapid heat-up and cool-down temperature
Model
AH-235W
AH-235
AH-255W
AH-255
AH-270W
AH-270
AH-2A0W
AH-2A0
Temperature range℃
-25℃~200℃
Control Mode
Feed forward PID +Our special dynamic control calculation, PLC controller
Communication protocol
MODBUS RTU Protocol, RS 485 Interface
Temp. Control optional
Material process control
Program Editor
20 programs, each program can edit 45 steps.
Temperature feedback
Heat-conducting medium :PT100
Material process:PT100
Refrigeration host
Can set refrigeration host temperature independently
Temp. accuracy
±1℃
±1℃
±1℃
±1℃
Heating power
3.5kW
5.5kW
7kW
10kW
Cooling
capacity
200℃
3.5kW
5.5kW
7kW
10kW
100℃
3.5kW
5.5kW
7kW
10kW
20℃
3.5kW
5.5kW
7kW
10kW
-5℃
3 kW
4.5kW
6.6kW
8kW
-20℃
1.8kW
2.8kW
3.8kW
4.6kW
Circulation pump
Max35L/min
2BAR
Max50L/min
2BAR
Max50L/min
2BAR
Max50L/min
2BAR
Compressor
Copeland
Copeland
Copeland
Copeland
Expansion valve
Danfoss
Optional
7-inch color touch screen controller, temperature curve record, data export to excel format.
Self-diagnosis function; freezer overload protection; high pressure switch, overload relay, thermal protection device,
liquid low level protection, high temperature protection and temperature fault protection.
Closed
circulation system
The whole system is full closed circulation, there is no oil mist at high temperature and no water vapor at low temperature,
pressure do not rise up when system is running. The system will supplement oil automatically at low temperature.
Refrigerant
R-404A
Connection size
DN20
DN20
DN20
DN20
Water-cooled type W
(cooling water at 20℃)
800L/H
1.5bar~4bar
1200L/H
1.5bar~4bar
2000L/H
1.5bar~4bar
2900L/H
1.5bar~4bar
Dimension
water-cooled
600*700*1250
600*700*1250
700*700*1250
700*800*1500
air-cooled
620*680*1450
620*680*1450
750*750*1650
1100*800*1650
Weight
water-cooled
160kg
235kg
315kg
390kg
air-cooled
195kg
265kg
355kg
425kg
Power
AC 380V 50HZ
6kW (max)
AC 380V 50HZ
8kW (max)
AC 380V 50HZ
11kW (max)
AC 380V 50HZ
14kW (max)
Case material
SUS 304
SUS 304
SUS 304
SUS 304
Contact Us
Tel: (+86) 400 610 1188